Csb-battery UPS12580 User Manual

Browse online or download User Manual for Power suppliers Csb-battery UPS12580. CSB Battery UPS12580 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Cells Per Unit 6
Voltage Per Unit 12
Capacity
580W @ 5min-rateto Watt(1.60V)/pcs @25
(77 )
Weight Approx. 2.83 kg(6.24 lbs)
Maximum Discharge Current 130A(5sec)
Internal Resistance Approx. 12.5m
Operating Temperature Range
Nominal Operating Temperature Range 25
3 (77 5 )
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25
(77 )
Recommended Maximum Charging 3.76A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25
(77 )
Self Discharge CSB Batteries can be stored for more than 6 months at
25
(77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15
~40 ( 5 ~104 )
F2-Faston Tab 250
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
UPS12580
Specification
Powered by
UPS 12580 is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 5 years
in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
98.3±1.0(3.87± 0.04) 94.0±1.0 (3.70±0.04) 151.0±2.0 (5.95±0.08) 65.0±1.0 (2.56±0.04)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 95.1 75.5 63.4 54.1 47.2 42.3 38.5 32.3 23.0 18.3 13.2 7.42 5.31
1.67V 85.3 71.0 60.2 51.7 45.6 41.2 37.6 31.7 22.7 18.1 13.0 7.33 5.20
1.70V 81.1 68.3 58.4 50.4 44.6 40.4 37.1 31.3 22.7 18.0 12.9 7.24 5.17
1.75V 73.6 62.6 53.7 47.2 42.2 38.5 35.6 30.1 22.1 17.5 12.7 7.11 5.03
1.80V 66.1 56.8 48.8 43.2 39.3 36.3 33.2 28.4 21.1 16.9 12.4 6.92 4.91
1.85V 59.4 49.7 43.5 39.3 36.3 32.9 30.3 26.1 19.6 15.8 11.7
6.61 4.70
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
908 774 663 580 516 469 427 361 261 208 150 84.2 59.3
1.67V
877 748 643 565 504 462 420 356 261 206 149 84.0 58.9
1.70V
859 730 630 556 499 453 414 353 258 206 149 83.6 58.8
1.75V
808 688 601 538 481 441 402 343 254 203 148 83.1 58.4
1.80V
750 640 568 505 458 419 383 329 245 197 145 81.7 57.6
1.85V
674 586 514 463 424 384 352 305 229 186 138 78.9 55.6
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.