Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
Cells Per Unit 6
Voltage Per Unit 12
Capacity 52Ah @ 20hr-rate to 1.75V per cell @25
(77 )
Weight Approx. 18.3 kg (40.35 lbs)
Maximum Discharge Current 500A(5sec)
Internal Resistance Approx. 5.5 m
Operating Temperature Range
Nominal Operating Temperature Range 25
3 (77 5 )
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25
(77 )
Recommended Maximum Charging 15.6 A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25
(77 )
Self Discharge CSB Batteries can be stored for more than 6 months at
25
(77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
B4-L terminal to accept M6 nut & bolt
Container Material
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15
~40 ( 5 ~104 )
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
EVX 12520
12V 52Ah
Specification
Powered by
EVX 12520 is designed specially for electric vehicles,
such as electric golf cart, electric wheelchair, mower,
dust collector...etc. It has high cycling life, high
efficiency and long service life.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
219.3±2.0 (8.63±0.08) 201.3±2.0 (7.93±0.08) 248.0±2.0 (9.76±0.08) 138.4±1.5 (5.45±0.06)
F.V/Time 30MIN 60MIN 90MIN 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V
64.9 36.8 27.0 21.0 14.8 11.7
9.60 6.60 5.42 2.84
1.67V
63.5 36.4 26.8 20.8 14.6 11.6
9.52 6.52 5.36 2.80
1.70V
62.1 35.8 26.5 20.6 14.5 11.5
9.45 6.45 5.29 2.76
1.75V
60.6 35.2 26.1 20.3 14.3 11.4
9.37 6.34 5.21 2.72
1.80V
59.2 34.7 25.6 20.1 14.2 11.3
9.26 6.22 5.12 2.68
1.85V
57.8 34.2 25.1 19.9 14.1 11.2
9.16 6.11 5.03 2.62
F.V/Time 30MIN 60MIN 90MIN 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V
668 386 284 221 154 124
102 70.9 58.7 33.6
1.67V
656 382 281 219 153 123
101 70.2 58.1 33.1
1.70V
645 378 277 217 152 122
100 69.4 57.4 32.5
1.75V
631 372 273 214 151 121
99.0 68.6 56.7 31.8
1.80V
615 368 269 212 150 120
98.1 67.6 55.8 31.1
1.85V
598 363 264 209 149 119
97.0 66.1 54.8 30.4
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.