Cells Per Unit 6
Voltage Per Unit 12
Capacity
240W @ 5min-rateto Watt(1.60V)/pcs @25°C (77°F)
Weight Approx. 1.45 kg(3.2 lbs)
Maximum Discharge Current 100/130A(5sec)
Internal Resistance Approx. 32mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at
Recommended Maximum Charging 2.0A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge CSB Batteries can be stored for more than 6 months at
Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge:
Charge:
Storage:
F1/F2-Faston Tab 180/250
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
UPS12240 6
Specification
Powered by
UPS 12240 6 is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 5 years
in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
98.3±1.0 (3.87±0.04) 94.0±1.0 (3.70±0.04) 151.0±2.0 (5.94±0.08) 51.0±1.0 (2.01±0.04)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by URS according to ISO 9001,ISO 14001.
The system of manufacturer was certified
25°C (77°F)
25°C (77°F)
25°C (77°F).
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
42.4 32.6 27.2 23.6 20.6 18.3 16.1 13.5 9.89 7.93 5.80 3.35 2.41
1.67V
37.4 30.3 26.0 22.7 20.0 17.7 15.9 13.3 9.77 7.88 5.77 3.34 2.40
1.70V
35.2 29.1 25.2 22.0 19.7 17.4 15.6 13.2 9.67 7.86 5.75 3.31 2.38
1.75V
31.4 26.7 23.5 20.8 18.5 16.6 14.9 12.8 9.57 7.73 5.69 3.28 2.36
1.80V
27.7 24.4 21.3 19.1 16.9 15.2 14.0 12.1 9.22 7.48 5.55 3.22 2.32
1.85V
24.0 21.0 19.0 16.7 15.0 13.7 12.6 11.0 8.53 6.96 5.28 3.08 2.23
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
383 321 275 240 213 192 177 151 112.0 90.1 66.1 38.5 28.1
1.67V
362 306 264 233 208 189 174 149 111.0 89.7 65.7 38.4 28.0
1.70V
350 297 258 228 205 187 171 148 110.0 89.4 65.6 38.3 27.9
1.75V
324 277 243 217 196 180 166 144 109.0 88.1 65.1 38.1 27.8
1.80V
296 254 226 201 184 170 156 136 105.0 85.5 63.7 37.5 27.4
1.85V
258 228 203 184 170 154 143 127 97.8 79.7 61.3 36.1 26.4
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.