Csb-battery MU1000S User Manual

Browse online or download User Manual for Power suppliers Csb-battery MU1000S. CSB Battery MU1000S User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Cells Per Unit 1
Voltage Per Unit 2
Capacity 1000A h @ 10hr-rate to 1.80V per cell @25
(77 )
Weight Approx. 62.5 kg(137.8 lbs)
Maximum Discharge Current 6000A(5sec)
Internal Resistance Approx. 0.35 m
Operating Temperature Range Discharge: -20 ~50 (-4 ~122 )
Charge: 0
~40 (32 ~104 )
Storage: -20
~40 (-4 ~104 )
Nominal Operating Temperature Range 25
3 (77 5 )
Float Charging Voltage
Recommended Maximum Charging 300A
Current Limit
Equalization and Cycle Service
Terminal
Pb-Ca-Sn Alloy(Recessed Terminal)
Container Material
The container and cover are made of flame retardant
plastics which meet UL 94-V0 specifications.
The oxygen index level is higher than 28.
2.23 0.02/Cell at 25 (77 ) Temp.
Coefficient 3.3mV/
( 1.8mV/ )
3.3mV/ ( 1.8mV/ )
2.35V Temps coefficient
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
MU 1000
2V 1000Ah
MU1000 is a long service life battery up to 20
years expected life under normal float charge.
As with all CSB batteries , all are rechargeable,
highly efficient , leak proof and maintenance free.
Specification
Powered by
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
497±3 (19.57±0.12) 463±3 )21.0±77.6( 3±271)21.0±32.81( 303±3 (11.93±0.12)
F.V/Time 30MIN 60MIN 90MIN 2HR 3HR 4HR 5HR 6HR 8HR 10HR
1.60V
1087
678 509 417 313 246 205 175 137 112
1.67V
1042
662 498 407 306 242 200 172 134 110
1.70V
983
637 483 394 295 235 194 167 130 106
1.75V
901
602 459 377 283 227 188 162 127 104
1.80V
807
553 427 355 267 216 179 155 122 100
1.83V
714
503 394 331 250 204 169 146 117 95.0
F.V/Time 30MIN 60MIN 90MIN 2HR 3HR 4HR 5HR 6HR 8HR 10HR
1.60V
1707
1173 886 734 554 438 369 317 249 205
1.67V
1678
1152 872 724 548 436 364 315 247 204
1.70V
1642
1121 855 709 534 430 357 311 243 199
1.75V
1541
1066 817 682 515 418 348 303 239 197
1.80V
1420
990 769 650 491 402 335 291 231 190
1.83V
1307
920 725 619 470 388 323 279 225 183
PP V 0
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Page view 0
1 2

Summary of Contents

Page 1 - 2V 1000Ah

Cells Per Unit 1Voltage Per Unit 2Capacity 1000A h @ 10hr-rate to 1.80V per cell @25(77 )Weight Approx. 62.5 kg(137.8 lbs)Maximum Discharge Current 60

Page 2 - 2V 1000Ah

tiGas recombination efficiencyCA(Min-Hrs)MU 10002V 1000AhGLOBAL HQ CSB BATTERY CO., LTD. (TAIWAN) Tel : +886-2-2880-5600 Fax : +886-2-2888-3300mail :

Comments to this Manuals