Page view 0
Cells Per Unit 6
Voltage Per Unit 12
Capacity 40A h @ 20hr-rate to 1.75V per cell @25°C (77°F)
Weight Approx. 12.63 kg(27.84 lbs)
Maximum Discharge Current 400A(5sec)
Internal Resistance Approx. 8.1mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 12A
Current Limit
Equalization and Cycle Service
Self Discharge CSB Batteries can be stored for more than 6 months at
25°C
(77°F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal B2-L terminal or Recessed type to accept M5 bolt
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge:
-15°C~50°C( 5°F~122°F)
Charge:
Storage:
Constant Power Discharge Characteristics Unit:W(25°,77°F)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GP 12400
12V 40Ah
Specification
Powered by
GP 12400 is a general purpose battery up to 5 years in standby
service or more than 260 cycles at 100% discharge in cycle
service. As with all CSB batteries, all are rechargeable, highly
efficient, leak proof and maintenance free.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
170±2 (6.69±0.08) 168.5±2 (6.63±0.08) 197±2 (7.76±0.08) 165±2 (6.5±0.08)
13.5 to 13.8 VDC/unit Average at 25°C (77°F)
14.4 to 15.0 VDC/unit Average at 25°C (77°F)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
176 113 85.0 51.8 30.6 22.2 17.7 12.6 8.01 5.25 4.28 2.21
1.67V
157 105 81.0 50.8 30.3 22.1 17.6 12.5 7.98 5.19 4.19 2.11
1.70V
149 101 78.7 50.1 30.2 21.9 17.5 12.4 7.96 5.17 4.16 2.08
1.75V
135 95.0 75.5 49.0 30.0 21.8 17.4 12.3 7.93 5.10 4.09 2.00
1.80V
121 88.3 71.7 47.6 29.8 21.7 17.3 12.2 7.88 5.03 4.03 1.93
1.85V
107 81.7 67.8 46.2 29.4 21.5 17.2 12.1 7.85 4.96 3.96 1.85
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
2110 1350 1020 622 367 266 212 151 96.1 63.0 51.3 26.5
1.67V
1886 1259 972 606 364 264 211 150 95.7 62.3 50.4 25.4
1.70V
1790 1214 945 600 363 263 210 149 95.5 62.0 50.0 24.9
1.75V
1620 1140 902 585 360 262 209 148 95.2 61.2 49.2 24.1
1.80V
1450 1060 860 571 357 260 208 147 94.8 60.4 48.3 23.2
1.85V
1280 980 814 555 353 258 207 146 94.2 59.6 47.5 22.4
-15°C~40°C
-15°C~40°C
( 5°F~104°F)
( 5°F~104°F)
25°C±3°C (77°F±5°F)
RA1403
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Drawing of recessed terminal
Page view 0
1 2

Summary of Contents

Page 1 - GP 12400

Cells Per Unit 6Voltage Per Unit 12Capacity 40A h @ 20hr-rate to 1.75V per cell @25°C (77°F)Weight Approx. 12.63 kg(27.84 lbs)Maximum Discharge Curren

Page 2 - 12V 40Ah

Charge Voltage(V/Cell)ApplicationTemperature Set Point Allowable RangeMax.Charge CurrentCycle Use25(77 )2.45 2.40~2.50Standby25(77 )2.275 2.25~2.300.3

Comments to this Manuals

No comments