Csb-battery GPL12750 User Manual

Browse online or download User Manual for Power suppliers Csb-battery GPL12750. CSB Battery GPL12750 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
Cells Per Unit 6
Voltage Per Unit 12
Capacity 75 Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 25.6 kg(56.44 lbs)
Maximum Discharge Current 800A(5sec)
Internal Resistance Approx. 4.5 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 22.5 A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge
CSB Batteries can be stored for more than 6 months at
25°C (77°F). Please charge batteries before using . For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge:
Charge:
Storage:
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GPL 12750
12V 75Ah
Specification
Powered by
GPL 12750 is a general purpose battery up to 10 years in standby
service or more than 260 cycles at 100% discharge in cycle
service . As with all CSB batteries, all are rechargeable , highly
efficient , leak proof and maintenance free.
13.5 to 13.8 VDC/unit Average at
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
214.2±2.5 (8.43±0.1) 211.2±2.5 (8.31±0.1) 261±2.5 (10.28±0.1) 168.5±2 (6.63±0.08)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
@25°C (77°F)
25°C (77°F)
25°C (77°F)
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
298 198 149 87.5 53.5 38.8 30.9 21.9 14.5 9.51 7.85 4.15
1.67V
274 191 146 86.7 53.2 38.6 30.7 21.7 14.4 9.40 7.78 4.13
1.70V
265 187 144 86.1 52.4 38.1 30.5 21.5 14.3 9.34 7.76 4.11
1.75V
234 170 139 84.4 51.4 37.4 29.9 21.4 14.1 9.32 7.63 4.04
1.80V
210 158 131 81.9 50.2 36.8 29.5 21.0 13.8 9.17 7.55 3.97
1.85V
183 145 118 77.0 47.5 34.9 28.1 20.3 13.5 8.88 7.26 3.82
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
3013 2127 1654 1003 614 456 370 261 173 116 93.5 49.7
1.67V
2818 2060 1635 996 612 452 365 260 172 115 92.9 49.4
1.70V
2729 2022 1609 994 610 450 363 259 171 114 92.7 49.3
1.75V
2553 1927 1558 976 603 447 361 257 170 113 92.3 49.0
1.80V
2371 1815 1478 949 592 440 356 254 168 111 91.0 48.7
1.85V
2075 1667 1348 904 572 422 341 245 162 107 87.5 47.1
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Page view 0
1 2

Summary of Contents

Page 1 - GPL 12750

I2-Thread lead alloy recessed terminal to accept M6/M8 boltPolypropylene(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon

Page 2 - GPL12750

Charge Voltage(V/Cell) Application Temperature Set Point Allowable Range Max.Charge Current Cycle Use 25(77 ) 2.45 2.40~2.50 Standby 25(77 ) 2.275

Comments to this Manuals