I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
Cells Per Unit 6
Voltage Per Unit 12
Capacity 88 Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 29.7 kg(65.48 lbs)
Maximum Discharge Current 800A(5sec)
Internal Resistance Approx. 4.5 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 26.4A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge
CSB Batteries can be stored for more than 6 months at
25°C(77°F). Please charge batteries before using . For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge:
Charge:
Storage:
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GPL 12880
12V 88Ah
Specification
Powered by
GPL 12880 is a general purpose battery up to 10 years in standby
service or more than 260 cycles at 100% discharge in cycle
service . As with all CSB batteries, all are rechargeable , highly
efficient , leak proof and maintenance free.
13.5 to 13.8 VDC/unit Average at
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
214.3±2.5 (8.44±0.1) 211.3±2.5 (8.32±0.1) 308.7±2.5 (12.15±0.1) 169±2 (6.65±0.08)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
@25°C (77°F)
25°C (77°F)
25°C (77°F)
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
349 232 175 103 62.8 45.5 36.3 25.6 17.0 11.2 9.21 4.87
1.67V
321 225 171 102 62.4 45.2 36.0 25.5 16.9 11.1 9.12 4.84
1.70V
311 219 169 101 61.4 44.8 35.7 25.2 16.8 11.0 9.10 4.83
1.75V
274 199 163 99.0 60.3 43.9 35.1 25.1 16.6 10.9 8.96 4.74
1.80V
246 186 154 96.1 58.8 43.1 34.6 24.6 16.2 10.8 8.85 4.66
1.85V
215 170 138 90.3 55.8 41.0 32.9 23.8 15.8 10.4 8.51 4.48
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
3535 2496 1941 1177 720 535 434 306 203 136 110 58.3
1.67V
3307 2417 1919 1169 719 531 428 305 202 135 109 57.9
1.70V
3202 2373 1888 1166 716 529 426 304 201 134 108 57.8
1.75V
2995 2261 1828 1145 707 524 424 301 200 132 107 57.5
1.80V
2782 2129 1734 1113 694 516 418 298 198 130 106 57.1
1.85V
2434 1955 1581 1061 671 495 400 287 190 125 103 55.3
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Page view 0
1 2

Summary of Contents

Page 1 - GPL 12880

I2-Thread lead alloy recessed terminal to accept M6/M8 boltPolypropylene(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon

Page 2 - GPL12880

Charge Voltage(V/Cell) Application Temperature Set Point Allowable Range Max.Charge Current Cycle Use 25(77 ) 2.45 2.40~2.50 Standby 25(77 ) 2.275

Comments to this Manuals

No comments