Cells Per Unit 6
Voltage Per Unit 12
Capacity 90W @ 15min-rate to 1.67V per cell @25
(77 )
Weight Approx.
6.80 kg(14.99 lbs)
Maximum Discharge Current 300A(5sec)
Internal Resistance Approx. 9.5m
Operating Temperature Range
Nominal Operating Temperature Range 25
3 (77 5 )
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25
(77 )
Recommended Maximum Charging 9A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25
(77 )
Self Discharge CSB Batteries can be stored for more than 6 months at
25
(77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15
~40 ( 5 ~104 )
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
HR 1290W
12V 90W
Specification
Powered by
HR 1290W is specially designed for high efficient
discharge application. Its characteristics are high energy
density, small footprint and high discharge efficiency. It can
be used for more than 260 cycles at 100% discharge in cycle
service, up to 5 years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
167.0±2.0 (6.57±0.08) -- 181.0±2.0 (7.12±0.08) 76.2±1.0 (3.00±0.04)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
177 124 95.8 79.4 68 48.7 38.4 27.3 15.8 11.5
1.67V
156 114 90.2 77.6 65.2 48.4 38.1 27 15.7 11.4
1.70V
147 109 87.8 76.4 63.9 47.6 37.7 26.9 15.6 11.3
1.75V
131 102 82.9 72.8 61.1 46.2 37 26.3 15.5 11.2
1.80V
115 92.5 77.2 67.7 58 44 35.5 25.5 15.2 11.1
1.85V
98.6 82.9 70.8 60.8 53.3 40.7 32.6 23.8 14.5 10.6
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
1701 1282 1041 868 753 544 429 309 183 133
1.67V
1570 1193 989 850 734 540 428 307 182 132
1.70V
1509 1155 962 838 726 534 426 305 181 131
1.75V
1398 1087 913 802 704 520 416 300 179 130
1.80V
1282 1011 862 756 665 501 402 295 177 129
1.85V
1166 926 797 687 608 461 375 277 168 124
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.