Cells Per Unit 6
Voltage Per Unit 12
Capacity 34W @ 15min-rate to 1.67V per cell @25
(77 )
Weight Approx.
2.5 kg(5.51 lbs)
Maximum Discharge Current 100/130A(5sec)
Internal Resistance Approx. 19 m
Operating Temperature Range
Nominal Operating Temperature Range 25
3 (77 5 )
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25
(77 )
Recommended Maximum Charging 3.4A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25
(77 )
Self Discharge CSB Batteries can be stored for more than 6 months at
25
(77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15
~40 ( 5 ~104 )
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
HR 1234W
12V 34W
Specification
Powered by
HR 1234W is specially designed for high efficient
discharge application. Its characteristics are high energy
density, small footprint and high discharge efficiency. It can
be used for more than 260 cycles at 100% discharge in cycle
service, up to 5 years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
100.5±1.5 (3.96±0.06) 94.3±1.0 (3.71±0.04) 151.0±2.0 (5.94±0.08) 65.0±1.0 (2.56±0.04)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
73.8 49.2 36.8 29.7 25.4 18.5 14.6 10.5 5.99 4.25
1.67V
65.8 44.8 34.4 28.2 24.2 17.8 14.1 10.3 5.86 4.15
1.70V
62.2 42.9 33.3 27.5 23.6 17.4 13.8 10.1 5.80 4.11
1.75V
56.3 39.8 31.6 26.2 22.7 16.8 13.5 9.90 5.69 4.05
1.80V
50.3 36.4 29.7 24.9 21.7 16.2 13.1 9.66 5.60 3.99
1.85V
43.3 32.9 27.6 23.5 20.7 15.6 12.7 9.39 5.50 3.92
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
706 506 395 328 286 211 169 124 71.7 50.8
1.67V
645 470 376 315 276 205 165 121 70.5 50.1
1.70V
618 454 366 308 270 202 163 120 70.0 49.6
1.75V
571 426 350 296 260 196 160 118 69.0 49.0
1.80V
524 400 333 285 250 191 156 116 68.1 48.3
1.85V
478 376 316 273 241 186 152 114 67.0 47.7
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.